Prosoft-technology 5201-MNET-101S Manual de usuario Pagina 103

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 159
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 102
IEC-101 Slave ProLinx Communication Gateway Reference
IEC 60870-5-101 v3 Slave (Firmware version 3.xx) Protocol Manual
ProSoft Technology, Inc. Page 103 of 159
August 6, 2010
And if the parameter offsets are configured as follows:
It would imply that the parameter points would be configured as follows:
M_ME_NA
Monitored Measured Normalized Point Associated Parameter Point
400 2400
401 2401
402 2402
403 2403
404 2404
So, in order to send change the deadband for the M_ME_NA point 400, the
Master would send a command type 110 to point 2400:
Vista de pagina 102
1 2 ... 98 99 100 101 102 103 104 105 106 107 108 ... 158 159

Comentarios a estos manuales

Sin comentarios