IEC-101 Slave ProLinx Communication Gateway 101S Protocol Configuration
IEC 60870-5-101 v3 Slave (Firmware version 3.xx) Protocol Manual
ProSoft Technology, Inc. Page 47 of 159
August 6, 2010
2.13 [C_RC_NA_1]
This section defines the step command database. This information is sourced
from the remote Master and is transferred to the database.
You can associate a command with a monitored single-point database value to
coordinate the command/monitor operation. You must enter the correct M
ONITOR
POINT # and MONITOR DB ADDRESS values in the table. If the REQUIRE SELECT
parameter is not set to zero, a select command must be received before an
execute command will be processed.
This section takes the following parameters:
P
OINT #
DB
ADDRESS
M
ONITOR POINT #
M
ONITOR DB ADDRESS
Each point consumes one byte. T
HE DB ADDRESS value corresponds to the byte
offset in the database.
The DB
ADDRESS should be located in a database area that is being constantly
moved from the Master to the gateway.
For additional information on how to set these parameters, see the Reference
chapter of this manual.
2.14 [C_BO_NA_1 104]
This section defines the Command 32-bit Bitstring Point database. This
information is sourced from the remote Master and is transferred to the database.
You can associate a command with a Monitored Double-Point database value to
coordinate the command/monitor operation. You must enter the correct Monitor
Point # and Monitor DB Address values in the table. If the Require Select
parameter is not set to zero, a select command must be received before an
execute command will be processed.
This section takes the following parameters:
Point #
DB Address
Monitor Point #
Monitor DB Address
Each point is four 8-bit bytes and the DB Address value corresponds to the
double word offset in the gateway memory database.
The DB address should be located in a database area that is being constantly
moved from the Master to the gateway.
For additional information on how to set these parameters, see the Reference
chapter of this manual.