IEC-101 Slave ProLinx Communication Gateway Reference
IEC 60870-5-101 v3 Slave (Firmware version 3.xx) Protocol Manual
ProSoft Technology, Inc. Page 85 of 159
August 6, 2010
M_BO_NA
A Monitored 32-Bit Bitstring Point occupies two words and uses double-word
addressing.
For example, if you configured the following points:
The following table describes how these points would be stored in the gateway
memory database.
Inf. Object Address Module Database Address
600 Words 2000 and 2001 (Double-word address 1000)
601 Words 2002 and 2003 (Double-word address 1001)
602 Words 2004 and 2005 (Double-word address 1002)