101S Protocol Configuration IEC-101 Slave ProLinx Communication Gateway
Protocol Manual IEC 60870-5-101 v3 Slave (Firmware version 3.xx)
Page 42 of 159 ProSoft Technology, Inc.
August 6, 2010
2.3 [M_SP_NA_1]
This section defines the monitored single-point database. This information is
sourced from the database and is transferred to the remote Master unit.
This section takes the following parameters:
P
OINT #
DB
ADDRESS
G
ROUPS (page 50)
IV
DB BIT
Each point consumes one bit (1 = On, 0 = Off state). The DB
ADDRESS VALUE
corresponds to the bit offset address in the database.
The DB
ADDRESS should be located in a database area that is being constantly
moved from the gateway to the Master.
For additional information on how to set these parameters, see the Reference
chapter of this manual.
2.4 [M_DP_NA_1]
This section defines the monitored dual-point database. This information is
sourced from the database and is transferred to the remote Master unit.
This section takes the following parameters:
P
OINT #
DB
ADDRESS
G
ROUPS (page 50)
IV
DB BIT
Each point consumes two bits (00 = intermediate, 01 = off, 10 = on and 11 =
intermediate). The DB
ADDRESS value corresponds to the bit offset address in
the database.
The DB
ADDRESS should be located in a database area that is being constantly
moved from the gateway to the Master.
For additional information on how to set these parameters, see the Reference
chapter of this manual.