IEC-101 Slave ♦ ProLinx Communication Gateway 101S Protocol Configuration
IEC 60870-5-101 v3 Slave (Firmware version 3.xx) Protocol Manual
ProSoft Technology, Inc. Page 49 of 159
August 6, 2010
2.17 [C_SE_NC_1]
This section defines the short-float setpoint database. This information is sourced
from the remote Master and is transferred to the database.
You can associate a command with a monitored single-point database value to
coordinate the command/monitor operation. You must enter the correct M
ONITOR
POINT # and MONITOR DB ADDRESS values in the table. If the REQUIRE SELECT
parameter is not set to zero, a select command must be received before an
execute command will be processed.
This section takes the following parameters:
P
OINT #
DB
ADDRESS
M
ONITOR POINT #
M
ONITOR DB ADDRESS
R
EQUIRE SELECT
Each point consumes two words. The
DB ADDRESS value corresponds to the
double-word offset in the database.
The
DB ADDRESS should be located in a database area that is being constantly
moved from the Master to the gateway.
For additional information on how to set these parameters, see the Reference
chapter of this manual.