PS69-DPM ♦ CompactLogix or MicroLogix Platform Contents
PROFIBUS DPV1 Master User Manual
ProSoft Technology, Inc. Page 107 of 130
October 1, 2014
The maximum length of a bus segment depends on the baud rate used. Only PROFIBUS
certified cable, preferably the cable type A, should be used.
6.1.4 Hardware Specifications
EC1-160P with integrated ASPC2
RS-485, max. 12 MBaud, potential free, according EN
50170
RS232, PS/2 Mini DIN female connector, 9600 Baud, non
isolated
max. 6 modules to the power supply module
Standard 1769 Single-slot module
EN 61000-4-4, 2 kV, 5 kHz
EN 61000-4-5, 2 kV common mode, 1 kV differential
mode
EN 61000-4-2, 4 kV contact, 8 kV air, 4 kV indirect
Radiated/ Conducted
Immunity
EN 61000-4-3, 10 V/m, 30...1000 MHz, 80% AM, 1 kHz
sinewave
EN 61000-4-6, 10 V, 0,15...30 MHz
Radiated/ Conducted
Emission
IEC 600068-2-6, 10-150 Hz, ± 0,75 mm, ± 1 g, 1
Octave/min
IEC 600068-2-27, 15 g, 11 ms
5 to 95% (non-condensing)