Contents PS69-DPM ♦ CompactLogix or MicroLogix Platform
User Manual PROFIBUS DPV1 Master
Page 88 of 130 ProSoft Technology, Inc.
October 1, 2014
Configuration data
size too large
Too much data transferred with
the CIP Message
Check if the overall length of the
requested command send with
the CIP message and the
consistency of all length
parameter within the requested
command is correct.
The requested object does not
exist within the module.
No answer message was
received.
General Error
Non specified error
occurred
General Error
Unknown command
The value in Req.Command is
unknown
The value Req.Command must
be initialized
DDLM_Slave_Diag
Service could be executed without an error
No response from the station
Check network wiring, check bus
address of slave or baud rate
support
Master not into the logical token ring
Check master DP-Address or
highest-station-address of the
Master. Examine bus wiring for
bus short circuits
Remote Address in request service out of
range
Check parameter in request
message
DDLM_Global_Control
The DDLM_Global_Control command initiates a multicast command on the PROFIBUS
network to all configured slaves. Therefore, this command is always assumed to be
successfully executed and no error will be placed in Cnf.Failure of the answer message.
Service was executed without an
error
DDLM_Set_Parameter
Service was executed without an
error
Slave has no buffer space left for the
requested service
Requested function of Master is not
activated within the Slave
Remote SAP is not activated