PS69-DPM ♦ CompactLogix or MicroLogix Platform Contents
PROFIBUS DPV1 Master User Manual
ProSoft Technology, Inc. Page 85 of 130
October 1, 2014
CIP Message Parameters for MSAC1_Write
Service Code "Bridge Message"
CIP Object "CIP_MSG_BRIDGE""
Reference to a Tag of type MSAC1_WRITE_REQUEST
Reference to a Tag of type
MSAC1_WRITE_CONFIRM
16 = Constant part of the service MSAC1_WRITE_REQUEST
x = Number of data to be transferred
MSAL1M_Alarm_Res
The MSAL1M_Alarm_Res request is used by the master to send a DPV1 Alarm response to
a slave device. The message acknowledges the alarm when the appropriate indication
appears in theDPV1 Alarm Indication (page 67) area. The information mapped to this area
must be used in the DPV1 Alarm Response message in order to process the alarm properly.
The mapping of this information shall be as follows.
MSAL1M_ALARM_RES_REQUEST
Command for Service MSAL1M_Alarm_Res
Address of the PROFIBUS Slave from DPV1 Alarm Indication
Register.
Slot Number from DPV1 Alarm Indication Register.
Sequence Number from DPV1 Alarm Indication Register.
Alarm Type from DPV1 Alarm Indication Register.
Alarm Spec from DPV1 Alarm Indication Register.
Comentarios a estos manuales