AN-X-DCSNet2 Page
59
At startup, the SYS LED sequence is:
• boot code starts – fast flashing red
• boot code loads a kernel – solid red
• if the configuration kernel is loaded, 2 red flashes followed by a
pause
• if the production kernel loads with no errors, solid green
NET LED – DCS Network Status
The NET LED indicates the status of the DCS network connection.
DCS Master
All drops operating correctly Solid green
No other drops Yellow
Network error Flashes red
DCS Slave
All drops operating correctly Solid green
No other drops Solid red
Network error Flashes red
DCS Diagnostic Counters
AN-X maintains standard DCS drop 0 diagnostic counters. Use
Automation Network/Monitor DCSNet in the web interface to view the
diagnostic counters.
The counters are:
Register Meaning
4-7 Drop status table
12 Local station’s drop number
14 Messages received
15 Receive timeouts
16 CRC errors
17 Overrun errors
18 Abort errors
19 Messages transmitted
20 Local station’s drop depth