5.4.2 Studio 5000 Adjustment (Optional)
This (optional) section allows you to tailor the ILX69-PBM input/output sizes to conserve
memory space in the CompactLogix™ processor.
Module Properties
1 With the CompactLogix controller in Offline mode, double-click on the MODULE PBM in
the I/O Configuration dialog to open the Module Properties.
2 In the Module Properties dialog, edit the Connection Parameters INPUT SIZE to the sum
of PROFIBUS Input words + 44.
In the example, there are 8 PROFIBUS input bytes, or (4) 16-bit words: 4 + 44 = 48.
For outputs, edit the Connection Parameters OUTPUT SIZE to the sum of PROFIBUS
Output words + 8.
In the example, there are 8 PROFIBUS output bytes, or (4) 16-bit words: 4 + 8 = 12.
3 Click APPLY, then OK.