ILX69PBM.CONTROL.DPV1.Read.Response
Name
Data Type
Value
Description
.Status
DINT
0x0000
ILX69-PBM Status
.Command
DINT
0x2211
Command code
.SlaveAddres
s
SINT
0 to 125
Slave address
.SlotNumber
SINT
0 to 255
Slot number
.Index
SINT
0 to 255
Index
.Length
SINT
0 to 255
Data length
.Data
SINT[100]
0 to 240
Data returned from slave. If an error is returned, the first 2
bytes contain the error code.
DPV1 Write Command
The MSG instruction format of a DPV1 write command and response is as follows.
ILX69PBM.CONTROL.DPV1.Write.Request.
Parameter
Data
Type
Value
Description
Status
DINT
0x0000
ILX69-PBM Status
Command
DINT
0x2212
Command code
SlaveAddress
SINT
0 to 125
Slave address
SlotNumber
SINT
0 to 255
Slot
Index
SINT
0 to 255
Index
Length
SINT
0 to 240
Data length
Data
SINT[100]
0 to 255
Data
ILX69PBM.CONTROL.DPV1.Write.Response.
Name
Data Type
Value
Description
Status
DINT
0x0000
ILX69-PBM Status
Command
DINT
0x2213
Command code
SlaveAddress
SINT
0 to 125
Slave address
SlotNumber
SINT
0 to 255
Slot
Index
SINT
0 to 255
Index
Length
SINT
0 to 255
Data length
Data
SINT[100]
0 to 240
Data returned from slave. If an error is returned, the first 2
bytes contain the error code.
ErrorDecode
SINT
128
DPV1 error detected
ErrorCode1
SINT
...
DPV1 Error Code 1
ErrorCode2
SINT
...
DPV1 Error Code 2
Reserved
SINT
-
N/A
Vista de pagina 85