ILX69-PBM ♦ CompactLogix or MicroLogix Platform Contents
PROFIBUS Master Communication Module User Manual
ProSoft Technology, Inc. Page 89 of 124
February 4, 2015
Configuration data size
too large
Too much data
transferred with the
CIP Message
Check if the overall length of
the requested command of
the CIP message and the
consistency of all length
parameters within the
requested command.
The requested object
does not exist within
the module.
No answer message
was received.
General Error
Non specified error
occurred
Contact technical support
General Error
Unknown command
The value in the
requested command is
unknown
The value in requested
command must be initialized
Slave Diagnostic
No response from
the station
Check network wiring, check bus address of
slave or baud rate support
Master not into the
logical token ring
Check ILX69-PBM address or highest-station-
address of the master. Examine bus wiring for
bus short circuits.
Remote address in
request service out
of range
Check parameter in request message
Set Slave Control
The Global Control command initiates a multicast command on the PROFIBUS network to
all configured slaves. This command is always assumed to be successfully executed and no
error will be placed in Cnf.Failure of the response message.