Contents ILX69-PBM ♦ CompactLogix or MicroLogix Platform
User Manual PROFIBUS Master Communication Module
Page 74 of 124 ProSoft Technology, Inc.
February 4, 2015
Slave Diag Failure
This byte reflects the status of the Slave Diagnostics request.
Service could be executed
without an error
No response from the
station
Check network wiring, bus address of slave, or baud rate
support.
Master not in the logical
token ring
Check master DP address or highest-station address of the
master. Examine bus wiring for short circuits.
Remote Address in
request service is out of
range
Check address parameter in diagnostics request.
Station Status_1
Slave device status information.
No response from slave device. The slave is non-existent.
Slave has incorrect parameterization
The extended diagnostics area is used
Unknown command is detected by the slave
Last parameterization telegram was faulty
Slave is controlled by another master
Station Status_2
Slave device status information (continued)
Parameter Request: Slave must be parameterized
This bit remains active until all diagnostics data has been
retrieved from the slave
This bit is always set by the slave
Slave watchdog is activated