Contents ILX69-PBM ♦ CompactLogix or MicroLogix Platform
User Manual PROFIBUS Master Communication Module
Page 90 of 124 ProSoft Technology, Inc.
February 4, 2015
DPV1 Read and Write
Service was executed
without an error
Slave has no buffer space left for the
requested service
Requested function of
master is not
activated within the
slave
Slave is not activated in its DPV1 support
No answer-data,
although the slave
must respond with
data
Slave has not sent any data back
No response of the
station
Check network wiring, check bus
address of slave or baud rate support
Master not in the
logical token ring
Check ILX69-PBM address or highest-
station-address of other masters.
Examine bus wiring to bus short circuits
No plausible reaction
of remote partner
Slave does not conform to DPV1 norm
Negative response
received, access
denied
Access denied to requested data. Check
ErrorCode1 and ErrorCode2 in response
message for further error information
Device is about to
stop the DPV1
communication or the
DPV1 is not in OPEN
state
DPV1 communications must be
configured to be activated by the device
Device has stopped
the DPV1
communication
automatically
A previously addressed slave has
responded with non-conform parameters
A previous service is
still in process
Wait for the outstanding answer first.
Parallel services are not allowed.
The length indicator
msg.data_cnt
exceeds maximum
configured size
Reduce length of message or enlarge
maximum buffer size in ProSoft fdt
Configuration Manager or in slave data
set
Wrong parameter in
request
Check msg.function or msg.device_adr
parameter of requested message
Correct the requested msg.b parameter
of message