Reference MVI46-DFNT ♦ SLC Platform
User Manual EtherNet/IP Client/Server Communication Module
Page 144 of 177 ProSoft Technology, Inc.
October 12, 2010
Verify that the CIP
radio-button is selected as the COMMUNICATION METHOD. The
PATH specifies the message route from the ControlLogix processor to the DFNT
module. Path elements are separated by commas. In the example path shown,
the first element is "Enet", which is the user-defined name given to the 1756-
ENET module in the chassis (you could substitute the slot number of the ENET
module for the name), the second element, "2", represents the Ethernet port on
the 1756-ENET module, and the last element of the path, "192.168.0.75", is the
IP address of the DFNT module, the target for the message.
More complex paths are possible if routing to other networks using multiple 1756-
ENET modules and racks. Refer to the Rockwell Automation Support
Knowledgebase for more information on Ethernet routing and path definitions.
Encapsulated PCCC Read Message
Read commands transfer data from the module to a ControlLogix processor. The
following encapsulated PCCC commands are supported from a ControlLogix
Processor:
PLC2 Unprotected Read
PLC5 Typed Read
PLC5 Word Range Read
PLC Typed Read
An example rung used to execute a read command is shown in the following
diagram:
The MESSAGE CONFIGURATION dialog box must be completed to define the data
set to transfer to the processor from the module. An example of the dialog box
follows: