Configuring the MVI46-DFNT Module MVI46-DFNT ♦ SLC Platform
User Manual EtherNet/IP Client/Server Communication Module
Page 34 of 177 ProSoft Technology, Inc.
October 12, 2010
Module Information Data Device Information Data
Column
#
1 2 3 4 5 6 7 8 9 10 11 12
Functio
n Code
Enabl
e
Code
Internal
Addres
s
Poll
Interval
Time
Coun
t
Swap
Code
IP
Address
Slot
Numbe
r
Funct
ion
Code
Function Parameters
FC 510 Code Register
Second
s
Count Code Node
510 File
Type
File
Numbe
r
Elemen
t
Sub-
Elemen
t
FC 511 Code Register
Second
s
Count Code Node
511 File
Type
File
Numbe
r
Elemen
t
Sub-
Elemen
t
IP Address = IP address of processor to reach
Slot Number = -1 for PLC5 & SLC, processor slot number of ControlLogix
The first part of the record is the Module Information, which relates to the
module. The second part contains information required to interface to the Server
device. An example of a command list section of the configuration file is shown in
the following illustration.
[DFNT Client 0 Commands]
#
# The file contains examples for a ControlLogix processor with the N7 file
# configured. This example uses SLC and PLC5 commands.
#
# LOCATION :
# DATE : 04/05/2000
# CONFIGURED BY: RAR
# MODIFIED :
#
# 1 2 3 4 5 6 7 8 9 10 11 12
# DB Poll Swap Func File File Elm Sub