Prosoft-technology MVI46-DFNT Manual de usuario Pagina 89

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 177
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 88
MVI46-DFNT ♦ SLC Platform Reference
EtherNet/IP Client/Server Communication Module User Manual
ProSoft Technology, Inc. Page 89 of 177
October 12, 2010
The format of the pass-through port configuration error word is as follows:
Bit Description Value
0 Invalid enable code 0x0001
1 Invalid local station ID 0x0002
2 Invalid protocol or termination type 0x0004
3 Invalid baud rate 0x0008
4 Invalid parity 0x0010
5 Invalid data bits 0x0020
6 Invalid stop bits 0x0040
7 0x0080
8 Invalid Use CTS Line selection 0x0100
9 Invalid retry count 0x0200
10 0x0400
11 0x0800
12 0x1000
13 0x2000
14 0x4000
15 0x8000
The format of the pass-through server configuration error word is as follows:
Bit Description Value
0 Invalid enable code 0x0001
1 Invalid busytimeout setting (< 100 milliseconds) 0x0002
2 0x0004
3 0x0008
4 0x0010
5 Invalid baud rate 0x0020
6 Invalid parity 0x0040
7 Invalid data bits 0x0080
8 Invalid stop bits 0x0100
9 0x0200
10 0x0400
11 0x0800
12 0x1000
13 0x2000
14 0x4000
15 0x8000
Vista de pagina 88
1 2 ... 84 85 86 87 88 89 90 91 92 93 94 ... 176 177

Comentarios a estos manuales

Sin comentarios