Reference MVI46-DFNT ♦ SLC Platform
User Manual EtherNet/IP Client/Server Communication Module
Page 80 of 177 ProSoft Technology, Inc.
October 12, 2010
Client Command List
In order for the client to function, the module's Client Command List must be
defined. This list contains up to 100 individual entries, with each entry containing
the information required to construct a valid command. This includes the
following:
Command enable mode ((0) disabled, (1) continuous or (2) conditional)
IP address of the remote server
Slot number for processor when interfacing with a SLC processor
Command Type - Read or Write command
Database Source and Destination Register Address - Determines where data
will be placed and/or obtained
Address information to access data in remote unit
Count - Select the number of words to be transferred
Poll Delay - (1/10