Prosoft-technology MVI46-DFNT Manual de usuario Pagina 150

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 177
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 149
Reference MVI46-DFNT ♦ SLC Platform
User Manual EtherNet/IP Client/Server Communication Module
Page 150 of 177 ProSoft Technology, Inc.
October 12, 2010
The T
ARGET DEVICE DATA TABLE ADDRESS must be set to a valid file element
(such as, N11:0) for SLC and PLC5 messages. For the PLC2 Unprotected Write
message, set the address to the database index (such as, 1000) to consider with
the command.
The MULTIHOP option must be set to YES. The MULTIHOP tab portion of the dialog
box must be completed as shown in the following window:
Set the IP address value to the module’s Ethernet IP address. You must press
the "Insert" key to add the second line for ControlLogix Backplane and set the
slot number to zero.
PLC5 Read Commands
Read commands transfer data to the PLC5 processor from the DFNT module. An
example rung used to execute a read command is shown in the following
diagram:
Vista de pagina 149
1 2 ... 145 146 147 148 149 150 151 152 153 154 155 ... 176 177

Comentarios a estos manuales

Sin comentarios