PLX8x-EIP-61850 Communication Gateway Start Here
Server to
IEC 61850 Client User Manual
ProSoft Technology, Inc. Page 11 of 167
July 2, 2015
1.4 Setting Jumpers
Jumper settings are located on the back of the module.
1.4.1 PLX81-EIP-61850
When the module is manufactured, the port selection jumpers are set to Mode 3.
You must set the jumpers to the correct position. The following diagram of the
back of the module describes the jumper settings.
Mode 3:
Setup Jumper: This is the top jumper. This must be jumpered when performing a
firmware upgrade or when downloading a configuration file to the module. For
normal operation, this jumper should be hung on only one pin (not jumpered).
Removing the jumper allows for better communications between the IEC and
EtherNet/IP driver and the jumper should be removed during running conditions.
Mode 2:
Default IP Jumper: This is the middle jumper. The default IP address of the
gateway is 192.168.0.250. Set this jumper to set the gateway's IP address back
to the default. For normal operation, this jumper should be hung on only one pin
(not jumpered).
Mode 1:
Reserved Jumper: This is the bottom jumper. It is reserved for internal ProSoft
Technology use only. For normal operation, this jumper should be hung on only
one pin (not jumpered).