
Reference PLX8x-EIP-61850 ♦ Communication Gateway
User Manual Server to
IEC 61850 Client
Page 98 of 167 ProSoft Technology, Inc.
July 2, 2015
{This table has been taken directly from the IEC 61850 Standard document.}
setMag
You must set this for APC (Controllable Analogue Set Point Information)
CDC.
operTm
The PLC user sends a command with operate time to the gateway, and the
gateway uses time activated control, e.g. it sends the time of operation to the
IED. The IED needs to support the time activated control.
origin.orCat
The orCat could have these values. The value depends upon the role of the
PLC. E.g. if the PLC is a station control, then this value never changes.
Control operation issued from an operator using a Client located at bay level
Control operation issued from an operator using a Client located at station
level
Control operation from a remote operater outside the substation (for example
network control center)
Control operation issued from an automatic function at bay level
Control operation issued from an automatic function at station level
Control operation issued from a automatic function outside of the substation
Control operation issued from a maintenance/service tool
Status change occurred without control action (for example external trip of a
circuit breaker or failure inside the breaker)
origin.orIdent
This is the address of the originator. The value you want depends upon the
role of the PLC.
ctlNum
This is of no consequence to the IED and only appears in reports. This is an
optional parameter. The ctlNum may be of interest to you when the Client
uses the same control number for a complete control sequence: select,
operate, …
Comentarios a estos manuales