Adding the Gateway to RSLogix 5000 PLX8x-EIP-61850 Communication Gateway
User Manual Server to
IEC 61850 Client
Page 50 of 167 ProSoft Technology, Inc.
July 2, 2015
3.4 Download the project to the processor to verify the connection
1 Save, and then download the project to the processor.
2 A yellow triangle in RSLogix 5000 means an error on connection. Check that
the Output size and Input size for the Class 1 connection in the gateway
configuration matches and the Comm Format is SINT. Try increasing RPI
time of module if the error persists.
3 If errors persist, re-download the configuration to make sure that the module
configuration matches the configured RSLogix 5000 program.
4 For additional troubleshooting, use the ProSoft EIP-61850 Configuration
Manager. Right-click the ProSoft Gateway bubble, and choose DIAGNOSTIC.
Class 1 displays the connection RPI time of processor and the IP address of
the ENBT. The open connection count starts at 1 and increments if the
connection to the processor is interrupted or there is a connection timeout.
State, open connection, and connection timeout are controlled by the code.
You can change the RPI and Ethernet IP in the ladder configuration in
RSLogix 5000 (right-click connection0 and choose PROPERTIES).