
Configuring the PLX8x-EIP-61850 Gateway PLX8x-EIP-61850 ♦ Communication Gateway
User Manual Server to
IEC 61850 Client
Page 42 of 167 ProSoft Technology, Inc.
July 2, 2015
When you right-click the IEC 61850 bubble representing that IED and choose
CONFIGURE, the IEC 61850 Mapping Tool window shows the previously
configured tags. If any of the previously configured Data Attributes for that
IED are now missing from the new CID, SCD, or ICD file that you just
imported, then those tags are highlighted in red. This lets you know that they
are not in the updated IED file.
3 Right-click the missing tag and choose DELETE. This removed the tag
mapping for the IED. Any corresponding mappings on the EtherNet/IP side
of the Gateway are also deleted.
4 When you have finished updating the mapping, choose MAPPING > SAVE to
save the changes.
5 Download the updated project to the gateway.
Comentarios a estos manuales