ILX34-AENWG ♦ POINT I/O Platform Procedures
Wireless Point I/O Adapter Setup Guide
Page 32 of 79 ProSoft Technology, Inc.
July 31, 2009
3.2.9 Example 1 - Direct Connection and Rack Optimization
This example configures your ILX34-AENWG for both direct connection and rack
optimization using RSLogix 5000 software.
You can mix communication formats for different I/O modules communicating
through the same adapter.
I/O modules set up to use rack optimization communicate at the rate of the
RPI configured for the ILX34-AENWG adapter.
I/O modules configured for direct communication communicate at their own
set RPI and ignore the ILX34-AENWG adapter RPI.
Attention: You must use series C POINT I/O modules with the ILX34-AENWG adapter. Series A
or B POINT I/O modules will not work with this adapter.
Add the Relay Output Module and Configure for Direct Connection
1 Right-click the ILX34-AENWG adapter under the I/O Configuration folder and
select N
EW MODULE.
2 In the S
ELECT MODULE dialog box, choose the 1734-OW2 relay output
module from the list, and click OK.