ILX34-AENWG POINT I/O Platform Procedures
Wireless Point I/O Adapter Setup Guide
Page 54 of 79 ProSoft Technology, Inc.
July 31, 2009
View Module Data
You can view module data and communication status in the controller tags in
RSLogix 5000. The following illustration shows the ILX34-AENWG configured
with the sample application.
ILX34_AENWG = the name you gave to your Ethernet adapter
# = slot number of POINT I/O module
C = configuration, I = input, O = output
Use the controller tags in your ladder program to read input data or write output
data.
Slot Status Bits: The Slot Status bits display the connection status for each of
the POINT I/O modules that use a rack-optimized connection.
Bit 0 is reserved for the adapter and always reports a value of 1.
Each of the other bits (1 to 63) correspond to a POINT I/O module that you
install in the POINT I/O backplane.
In this example, we configured the ILX34-AENWG adapter for both rack-
optimized and direct connections.
The slot status bits indicate that the module in slot 2 is operating correctly:
o 0=module participating with no errors and
o 1=module not participating or connection error (typically, module
removed/missing)