5204SE-MNET-PDPMV1 ProLinx Gateway Reference
Modbus TCP/IP to PROFIBUS DP-V1 Pass-Through Master User Manual
Page 206 of 235 ProSoft Technology, Inc.
December 22, 2009
4.6.7 Set Slave Mode Message Structure
Parameter Description
Command Initiator Application
Command Name FB_APPL_SET_SLAVE_MODE
Command Number 0003h
Fragmented No
Extended Header Data Fault information may be returned in the header of the response.
Command and Response Layout: Set Slave Mode
Command
Response
Message ID
(ID)
(ID)
Acyclic Message Status
Word
4002h
0002h
Command 0003h
0003h Set Slave Mode
Data size 0000h
0000h
Frame count 0001h
0001h
Frame number 0001h
0001h
Offset high 0000h
0000h
Offset low 0000h
0000h
Extended word 1 Slave
Address
Group Select
Slave
Address
Group Select
Extended word 2 Control
Command
Control
Command
Extended word 3 -
-
Extended word 4 -
-
Extended word 5 -
-
Extended word 6 -
-
Extended word 7 -
Extended Fault Information
Extended word 8
Fault Information
Acyclic Message Status Word
Refer to Acyclic Message Status Word (page 218).
Slave Address
Range 0 to 125; 127