5204SE-MNET-PDPMV1 ♦ ProLinx Gateway Procedures
Modbus TCP/IP to PROFIBUS DP-V1 Pass-Through Master User Manual
Page 48 of 235 ProSoft Technology, Inc.
December 22, 2009
2 This action opens the Unity Passthru Memory Map dialog box.
3 On the Memory Map dialog box, click E
XPORT PROCESSOR FILES. This will
create two Unity Pro import files, an .XSY file and a .XFM file. Both files must
be imported into the Unity Pro project for the application to work successfully.
4 Name the files (or accept the default names given by PCB), choose a location
on your hard drive where you wish the files to be stored, and then click S
AVE.