5204SE-MNET-PDPMV1 ProLinx Gateway Procedures
Modbus TCP/IP to PROFIBUS DP-V1 Pass-Through Master User Manual
Page 92 of 235 ProSoft Technology, Inc.
December 22, 2009
3.7.6 Download the Project to the M340 Processor
1 Open the PLC menu and then choose CONNECT. This action opens a
connection between the Unity Pro software and the processor, using the
address and media type settings you configured in the previous step.
2 On the PLC
menu, choose TRANSFER PROJECT TO PLC. This action opens
the
TRANSFER PROJECT TO PLC dialog box. If you would like the PLC to go to
"Run" mode immediately after the transfer is complete, select (check) the
PLC
RUN AFTER TRANSFER check box.
3 Click the T
RANSFER button to download the project to the processor. As the
project is transferred, Unity Pro reports its process in a P
ROGRESS dialog box,
with details appearing in a pane at the bottom of the window.
When the transfer is complete, place the processor in Run mode. The processor
will start scanning your process logic application.