5.6 Error Codes
The module error codes are listed in this section. Error codes returned from the
command list process are stored in the command list error memory region. A
word is allocated for each command in the memory area. The error codes are
formatted in the word as follows: The least-significant byte of the word contains
the extended status code and the most-significant byte contains the status code.
Use the error codes returned for each command in the list to determine the
success or failure of the command. If the command fails, use the error code to
determine the cause of failure.
Note: The Module Specific error codes (not DF1 compliant) are returned from within the module
and never returned from an attached DF1 slave device. These are error codes that are part of the
DF1 protocol or are extended codes unique to this module. The standard DF1 error codes can be
found in the DF1 Protocol and Command Set Reference Manual (Publication 1770-6.5.16) from
Rockwell Automation. The most common errors for the DF1 protocol are shown in the following
tables:
5.6.1 Local STS Error Codes
Code (Int) Code (Hex) Description
0 0x0000 Success, no error
256 0x0100 DST node is out of buffer space
512 0x0200 Cannot guarantee delivery (Link Layer)
768 0x0300 Duplicate token holder detected
1024 0x0400 Local port is disconnected
1280 0x0500 Application layer timed out waiting for response
1536 0x0600 Duplicate node detected
1792 0x0700 Station is offline
2048 0x0800 Hardware fault