5.1.3 Hardware Specifications
Specification Description
Form Factor Single Slot 1771 chassis compatible
BTR/BTW data transfer
Local or remote rack
Backplane current load 800 mA @ 5 V
Operating temperature 0 to 60°C (32 to 140°F)
Storage temperature -40 to 85°C (-40 to 185°F)
Shock 30g operational
50g non-operational
Vibration 5 g from 10150 Hz
Relative humidity 5% to 95% (non-condensing)
LED Indicators Module status
Backplane transfer status
Application status
Serial activity and error LED status
Configuration Serial port (CFG) DB-9M PC compatible
RS-232
Hardware handshaking
Ethernet Port (Ethernet
modules)
RJ45 Connector
Link and activity LED indicators
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz
for 60 s, applied as specified in section 5.3.2 of IEC
60950: 1991
Ethernet Broadcast Storm Resiliency = less than or
equal to 5000 [ARP] frames-per-second and less
than or equal to 5 minutes duration