PLC-5 Command Set Functions
Function
Code
Command Function Definition PLC5 SLC500 &
MicroLogix
Power-
monitor II
ControlLogix
100 0x0F 0x00 Word Range Write
(Binary Address)
X
X
101 0x0F 0x01 Word Range Read
(Binary Address)
X
X
102 0x0F 0x26 Read-Modify-Write
(Binary Address)
X
X
150 0x0F 0x00 Word Range Write
(ASCII Address)
X
X
151 0x0F 0x01 Word Range Read
(ASCII Address)
X
X
152 0x0F 0x26 Read-Modify-Write
(ASCII Address)
X
X
SLC-500 Command Set Functions
Function
Code
Command Function Definition PLC5 SLC500 &
MicroLogix
Power-
monitor II
ControlLogix
501 0x0F 0xA1 Protected Typed
Logical Read With
Two Address Fields
X
X
502 0x0F 0XA2 Protected Typed
Logical Read With
Three Address Fields
X X X
509 0x0F 0XA9 Protected Typed
Logical Write With
Two Address Fields
X
X
510 0x0F 0XAA Protected Typed
Logical Write With
Three Address Fields
X X X
511 0x0F 0XAB Protected Typed
Logical Write With
Mask (Three Address
Fields)
X
X
Each command list record has the same general format. The first part of the
record contains the information relating to the communication module and the
second part contains information required to interface to the DF1 or EtherNet/IP
slave device.