Diagnostics and Troubleshooting MVI71-DFNT ♦ PLC 5
User Manual EtherNet/IP Client/Server Communication Module
Page 48 of 175 ProSoft Technology, Inc.
February 3, 2011
If a configuration error is present for the pass-through port, the configuration error
word contains a value other than zero. The configuration error word bits have the
following definitions:
Bit Description Value
0 Invalid enable code 0x0001
1 Invalid local station ID 0x0002
2 Invalid protocol or termination type 0x0004
3 Invalid baud rate 0x0008
4 Invalid parity 0x0010
5 Invalid data bits 0x0020
6 Invalid stop bits 0x0040
7 0x0080
8 Invalid Use CTS Line selection 0x0100
9 Invalid retry count 0x0200
10 0x0400
11 0x0800
12 0x1000
13 0x2000
14 0x4000
15 0x8000
Correct any invalid data in the configuration for proper module operation. When
the configuration contains a valid parameter set, all the bits in the configuration
words are clear. This does not indicate that the configuration is valid for the user
application. Make sure each parameter is set correctly for the specific
application.
Refer to the Configuration/Debug menu for configuration error words.
If the APP, BP ACT and OK LEDs blink at a rate of every one-second, this
indicates a serious problem with the module. Call ProSoft Technology support to
arrange for repairs.