5.6.4 Module Specific Error (not DFNT Compliant)
Code (Int) Code (Hex) Description
-1 0xFFFF CTS modem control line not set before transmit
-2 0xFFFE Timeout while transmitting message
-10 0xFFF6 Timeout waiting for DLE-ACK after request
-11 0xFFF5 Timeout waiting for response after request
-12 0xFFF4 Reply data does not match requested byte count
-20 0xFFEC DLE-NAK received after request
-21 0xFFEB DLE-NAK sent after response
-200 0xFF38 DLE-NAK received after request